Aprašymas
Hybrid motor starter for reversing 3~ AC motors up to 550 V AC, 0.6 A output current, adjustable overload shutdown and safe emergency stop up to PLe/SIL 3 and SmartWire–DT™adapter as a set.
Product type | Hybrid motor starter |
Operating mode | 100% operating factor |
Number of phases | 3 |
Motor starter type | Reversing starter |
Maximum power dissipation for nominal condition | 0.4 W |
Switching frequency | ≤ 2 Hz (Load-dependent) |
Maximum power dissipation | 2.5 W |
Minimum power dissipation | 0.88 W |
Coordination type | 1 |
Supply | |
Rated control circuit supply voltage US | 24 V DC |
Control supply voltage range | 19.2 V DC … 30 V DC |
Rated control supply current IS | 40 mA |
Protective circuit | Surge protection |
Reverse polarity protection; Parallel polarity protection diode | |
Insulation characteristics | |
Rated insulation voltage | 500 V |
Rated surge voltage | 6 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC |
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC | |
Basic insulation (IEC 60947-1) at operating voltage 300 V AC … 500 V AC | |
Safe isolation (EN 50178) at operating voltage 300 … 500 V AC | |
Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Control | |
Input name | Control input right/left |
Rated actuating voltage UC | 24 V DC |
Triggering voltage range | 19.2 V DC … 30 V DC |
Rated actuating current IC | 5 mA |
Switching threshold | 9.6 V (“0” signal) |
19.2 V (“1” signal) | |
Switching level | < 5 V DC (For EMERGENCY STOP) |
Typical turn-off time | < 30 ms |
AC output | |
Rated operating voltage Ue | 500 V AC |
Operating voltage range | 42 V AC … 550 V AC |
Mains frequency | 50/60 Hz |
Load current range | 75 mA … 600 mA (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min. (for auto reset) |
Leakage current | 0 mA |
Protective circuit | Surge protection |
Acknowledge output | |
Note | Confirmation: floating change-over contact, signal contact |
Contact type | 1 changeover contact |
Switching capacity according to IEC 60947-5-1 | 3 A (230 V, AC15) |
2 A (24 V, DC13) |
Control circuits | |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 14 |
Tightening torque | 0.5 Nm … 0.6 Nm |
5 lbf-in. … 7 lbf-in. | |
Load circuit | |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 14 |
Tightening torque | 0.5 Nm … 0.6 Nm |
5 lbf-in. … 7 lbf-in. |
Status display | Yellow LED |
Operating voltage display | Green LED |
Error indication | Red LED |
Dimensional drawing | |
Width | 22.5 mm |
Height | 165 mm |
Depth | 114 mm |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -5 °C … 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m |
ATEX | |
Identification | II (2) G [Ex e] [Ex d] [Ex px] |
II (2) D [Ex t] [Ex p] | |
Certificate | PTB 07 ATEX 3145 |
UL approval | |
Certificate | NLDX.E228652 |
NRNT.E172140 | |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | ≤ 3 |
Note | Safe shutdown |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 2 |
Note | Motor protection |
Performance Level (ISO 13849) | |
Identification | e |
Note | Safe shutdown |
Category (ISO 13849) | |
Identification | ≤ 3 |
Note | Safe shutdown |
UL data | |
SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) | |
FLA | 0.6 A (480 V AC) |
Group installation | 20 A (class RK5, SCCR 5kA, #24 – 14 AWG max. solid and stranded) |
30 A (class CC or J, SCCR 100kA, #24 – 14 AWG max, solid and stranded) | |
Category code | NLDX / NRNT |
Standards/regulations | |
Standards/regulations | IEC 60947-1 |
EN 60947-4-2 | |
IEC 61508 | |
ISO 13849 |
Mounting type | DIN rail mounting |
Assembly instructions | alignable, for spacing see derating |
Mounting position | vertical (horizontal DIN rail, motor output below) |
Item number | 2903116 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Note | Made to Order (non-returnable) |
Sales Key | CK7 |
Product Key | CK7432 |
Catalog Page | Page 31 (C-7-2013) |
GTIN | 4046356712828 |
Weight per Piece (including packing) | 390 g |
Weight per Piece (excluding packing) | 276.9 g |
Customs tariff number | 85371099 |
Country of origin | DE |
ECLASS
ECLASS-9.0 | 27370905 |
ECLASS-10.0.1 | 27370905 |
ECLASS-11.0 | 27370905 |
ETIM
ETIM 8.0 | EC001037 |
UNSPSC
UNSPSC 21.0 | 25173900 |
22.5 mm wide|Safety level in accordance with IEC 61508-1: SIL 3, ISO 13849: PL e|Reduction in wiring|Long service life|Space saving|Adjustable current for bimetal function|Low-wear switching