Description
Hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 24 V DC input, 0.6 A output current, and emergency stop function.
Product type | Hybrid motor starter |
Operating mode | 100% operating factor |
Number of phases | 3 |
Service life electrical | 3x 107 cycles |
Maximum power dissipation for nominal condition | 1.5 W |
Reversing frequency | ≤ 2 Hz |
Maximum power dissipation | 1.5 W |
Minimum power dissipation | 1.1 W |
Coordination type | 1 |
Rated insulation voltage | 500 V |
Rated surge voltage | 6 kV |
Supply | |
Rated control circuit supply voltage US | 24 V DC |
Control supply voltage range | 19.2 V DC … 30 V DC |
Rated control supply current IS | 40 mA |
Protective circuit | Surge protection |
Reverse polarity protection; Parallel polarity protection diode |
Control | |
Rated actuating voltage UC | 24 V DC |
Triggering voltage range | 19.2 V DC … 30 V DC |
Switching threshold | 9.6 V (“0” signal) |
19.2 V (“1” signal) | |
Switching level | < 5 V DC (For EMERGENCY STOP) |
Typical turn-off time | < 30 ms |
AC output | |
Rated operating voltage Ue | 500 V AC |
Operating voltage range | 42 V AC … 550 V AC |
Rated operating current Ie | 0.6 A (AC-51) |
0.6 A (AC-53a) | |
Mains frequency | 50/60 Hz |
Load current range | 75 mA … 600 mA (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min. (for auto reset) |
Leakage current | 0 mA |
Residual voltage | < 0.3 V |
Protective circuit | Surge protection |
Acknowledge output | |
Note | Confirmation 01: floating changeover contact |
Control circuits | |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 14 |
Load circuit | |
Connection method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 14 |
Status display | Yellow LED |
Operating voltage display | Green LED |
Error indication | Red LED |
Width | 22.5 mm |
Height | 107 mm |
Depth | 114 mm |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C … 70 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | ≤ 3 |
Note | Safe shutdown |
Performance Level (ISO 13849) | |
Identification | e |
Note | Safe shutdown |
Category (ISO 13849) | |
Identification | ≤ 3 |
Note | Safe shutdown |
UL data | |
SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) | |
FLA | 0.6 A (480 V) |
Standards/regulations | |
Standards/regulations | DIN EN 50178 |
EN 60947 | |
Power station requirements | |
Standards/regulations | DWR 1300/ZXX01/DD/7080.8d |
Air clearances and creepage distances between the power circuits | |
Standards/regulations | DIN EN 50178 |
Assembly instructions | Can be aligned with spacing = 20 mm |
Mounting position | Vertical (horizontal DIN rail) |
Item number | 2900558 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Note | Made to Order (non-returnable) |
Sales Key | CK6 |
Product Key | CK7412 |
Catalog Page | Page 178 (IF-2011) |
GTIN | 4046356527781 |
Weight per Piece (including packing) | 300 g |
Weight per Piece (excluding packing) | 217.64 g |
Customs tariff number | 85364900 |
Country of origin | DE |
ECLASS
ECLASS-9.0 | 27370905 |
ECLASS-10.0.1 | 27370905 |
ECLASS-11.0 | 27370905 |
22.5 mm wide|Safety level in accordance with IEC 61508-1: SIL 3, ISO 13849: PL e|Space saving|Reduction in wiring|Long service life|3-phase loop bridges|Low-wear switching