Description
PLC-INTERFACE, consisting of a relay base and plug-in safety relay with force-guided contacts in accordance with DIN EN 61810-3, Push-in connection, 2 changeover contacts, forcibly actuated, Freewheeling diode, Input voltage: 24 V DC
Product type | Relay Module |
Application | Forcibly guided contacts |
Operating mode | 100% operating factor |
Mechanical service life | approx. 107 cycles |
B10d | 600000 Cycles (AC1; 250 V / 6 A; 1 NO) |
900000 Cycles (AC1; 250 V / 3 A; 1 NO) | |
1800000 Cycles (AC1; 250 V / 1,5 A; 1 NO) | |
180000 Cycles (AC15; 250 V / 3 A; 1 NO) | |
560000 Cycles (AC15; 250 V / 2 A; 1 NO) | |
4600000 Cycles (AC15; 250 V / 0,75 A; 1 NO) | |
360000 Cycles (DC13; 24 V / 3 A; 1 NO) | |
740000 Cycles (DC13; 24 V / 1,5 A; 1 NO) | |
4200000 Cycles (DC13; 24 V / 0,75 A; 1 NO) | |
Insulation characteristics | |
Overvoltage category | III |
Pollution degree | 2 |
Insulation | Safe isolation, reinforced insulation |
Test voltage Winding/contact | 4 kVrms (50 Hz, 1 min., winding/contact) |
Test voltage Changeover contact/changeover contact | 2.5 kVrms (50 Hz, 1 min., changeover contact/changeover contact) |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 6 kV |
Coil side | |
Nominal input voltage UN | 24 V DC |
Input voltage range | 20.2 V DC … 32.4 V DC (20 °C) |
Input voltage range in reference to UN | see diagram |
Typical input current at UN | 30 mA |
Typical response time | 10 ms |
Typical release time | 10 ms |
Coil voltage | 24 V DC |
Protective circuit | Freewheeling diode |
Operating voltage display | Yellow LED |
Switching | |
Contact type | 2 changeover contacts, forcibly actuated |
Type of switch contact | Single contact |
Drive and function | monostable |
Drive (polarity) | bipolar |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 5 V (10 mA) |
Limiting continuous current | 6 A |
Maximum inrush current | 6 A |
Min. switching current | 10 mA (5 V) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC) |
288 W (48 V DC) | |
88 W (110 V DC) | |
110 W (220 V DC) | |
1500 VA (250 V AC) | |
Switching capacity min. | 150 mW |
Switching capacity | 3 A (24 V, DC13) |
3 A (230 V, AC15) | |
Force-guided contacts in accordance with EN 61810-3 | Type B |
Connection method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section solid | 0.14 mm² … 2.5 mm² |
Conductor cross section flexible | 0.14 mm² … 2.5 mm² |
0.2 mm² … 2.5 mm² (Single ferrule) | |
2x 0.5 mm² … 1 mm² (TWIN ferrule) | |
Conductor cross section AWG | 26 … 14 |
Width | 14 mm |
Height | 80 mm |
Depth | 104 mm |
Ambient conditions | |
Degree of protection Relay | RT II (Relay) |
Degree of protection Relay base | IP20 (Relay base) |
Degree of protection Installation location | ≥ IP54 (Installation location) |
Ambient temperature (operation) | -20 °C … 60 °C |
Ambient temperature (storage/transport) | -20 °C … 85 °C |
Altitude | ≤ 2000 m |
UL, USA | |
Identification | UL 508 |
UL 508 Recognized | |
UL, USA / Canada | |
Identification | UL 508 |
UL 508 Recognized | |
Corrosive gas test | |
Identification | ISA-S71.04. G3 Harsh Group |
EN 60068-2-60 |
Standards/regulations | |
Standards/regulations | IEC 60947-5-1 |
DIN EN 61810-3 |
Mounting type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting position | any |
Item number | 2910537 |
Packing unit | 10 pc |
Minimum order quantity | 1 pc |
Sales Key | CK6 |
Product Key | CK623C |
Catalog Page | Page 370 (C-5-2019) |
GTIN | 4055626486055 |
Weight per Piece (including packing) | 77 g |
Weight per Piece (excluding packing) | 68 g |
Customs tariff number | 85364190 |
Country of origin | DE |
ECLASS
ECLASS-9.0 | 27371601 |
ECLASS-10.0.1 | 27371601 |
ECLASS-11.0 | 27371601 |
ETIM
ETIM 8.0 | EC001437 |
UNSPSC
UNSPSC 21.0 | 39122300 |