Primary-switched power supply unit, QUINT POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 15 V DC / 2 A
AC operation | |
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
Electric strength, max. | 300 V AC 30 s |
Typical national grid voltage | 120 V AC |
230 V AC | |
Voltage type of supply voltage | AC/DC |
Inrush current | < 15 A (at 25 °C) |
Inrush current integral (I2t) | < 0.03 A2s |
Inrush current limitation | < 5 A |
Frequency range (fN) | 50 Hz … 60 Hz -10 % … +10 % |
Mains buffering time | typ. 32 ms (120 V AC) |
typ. 32 ms (230 V AC) | |
Current consumption | 0.69 A (100 V AC) |
0.59 A (120 V AC) | |
0.31 A (230 V AC) | |
0.31 A (240 V AC) | |
Nominal power consumption | 96.3 VA |
Protective circuit | Transient surge protection; Varistor |
Typical response time | 300 ms |
Input fuse | 3.15 A (slow-blow, internal) |
Recommended breaker for input protection | 6 A … 16 A (Characteristic B, C or comparable) |
Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
< 0.17 mA | |
DC operation | |
Input voltage range | 110 V DC … 250 V DC -20 % … +10 % |
Voltage type of supply voltage | AC/DC |
Inrush current integral (I2t) | < 0.03 A2s |
Inrush current limitation | < 5 A |
Current consumption | 0.61 A (110 V DC) |
0.27 A (250 V DC) |
Efficiency | typ. 88.8 % (120 V AC) |
typ. 89.4 % (230 V AC) | |
Nominal output voltage | ± 15 V DC |
Nominal output current (IN) | 2 A (+) |
1.4 A (-) | |
Static Boost (IStat.Boost) | 2.5 A ((+) ≤ 40 °C) |
Dynamic Boost (IDyn.Boost) | 4 A ((+) ≤ 60 °C, 5 s) |
Feedback voltage resistance | ≤ 25 V DC |
Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
Control deviation | < 0.5 % (Static load change 10 % … 90 %) |
< 2 % (Dynamic load change 10 % … 90 %, (10 Hz)) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 60 mVPP (with nominal values) |
Short-circuit-proof | yes |
No-load proof | yes |
Output power | 51 W |
58.5 W | |
81 W | |
Maximum no-load power dissipation | < 1.4 W (120 V AC) |
< 2 W (230 V AC) | |
Power loss nominal load max. | < 6.6 W (120 V AC) |
< 6.1 W (230 V AC) | |
Crest factor | typ. 1.8 (120 V AC) |
typ. 2,2 (230 V AC) | |
Rise time | 50 ms (UOut = 10 % … 90 %) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal (configurable) | |
Digital | 0 V DC 15 V DC 24 mA |
Default | 15 V DC 24 mA 15 V DC for UOut > 0.9 x USet |
Input | |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Output | |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Signal | |
Connection method | Push-in connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
Types of signaling | LED |
Floating signal contact | |
Active signal output Out1 (digital, configurable) | |
Active signal output Out2 (analog, configurable) | |
Remote contact | |
Signal ground SGnd | |
Signal output | |
POut | > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting) |
UOut | > 0.9 x USet (LED lights up green) |
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
3 kV AC (routine test) | |
Switching frequency | 4 kHz … 70 kHz (Auxiliary converter stage) |
80 kHz … 190 kHz (Main converter stage) | |
30 kHz … 150 kHz (PFC stage) |
Product type | Power supply |
MTBF (IEC 61709, SN 29500) | > 1284000 h (25 °C) |
> 644000 h (40 °C) | |
> 231000 h (60 °C) | |
Insulation characteristics | |
Protection class | II |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 40 °C |
Time | 56000 h |
Additional text | 120 V AC |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 40 °C |
Time | 65000 h |
Additional text | 230 V AC |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 25 °C |
Time | 168000 h |
Additional text | 120 V AC |
Life expectancy (electrolytic capacitors) | |
Current | 2 A |
Temperature | 25 °C |
Time | 195000 h |
Additional text | 230 V AC |
Width | 45 mm |
Height | 106 mm |
Depth | 90 mm |
Installation dimensions | |
Installation distance right/left (active) | 15 mm / 15 mm (POut ≥50% ) |
Installation distance right/left (passive) | 5 mm / 5 mm (POut ≥50% ) |
Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
Installation distance top/bottom (active) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (passive) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≤50 %) |
Mounting type | DIN rail mounting |
With protective coating | No |
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing material | Plastic |
Type of housing | Polycarbonate |
Hood version | Polycarbonate |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
Climatic class | 3K22 (in accordance with EN 60721-3-3) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, ±2.5 mm amplitude; 15 Hz … 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6) |
Rail applications | EN 50121-3-2 |
EN 50121-4 | |
EN 50121-5 | |
IEC 62236-3-2 | |
IEC 62236-4 | |
IEC 62236-5 | |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Standard – Safe isolation | IEC 61558-2-16 |
IEC 61010-2-201 | |
Standard – safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
IEC 61010-2-201 (SELV) | |
Standard – Safety of transformers | EN 61558-2-16 |
Overvoltage category | |
EN 61010-1 | II (≤ 5000 m) |
EN 62477-1 | III (≤ 2000 m) |
Item number | 2904596 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Product Key | CMPI12 |
GTIN | 4055626255743 |
Weight per Piece (including packing) | 382.7 g |
Weight per Piece (excluding packing) | 369 g |
Country of origin | VN |
ECLASS
ECLASS-9.0 | 27040701 |
ECLASS-10.0.1 | 27040701 |
ECLASS-11.0 | 27040701 |
ETIM
ETIM 8.0 | EC002540 |
UNSPSC
UNSPSC 21.0 | 39121000 |
Starting of heavy loads with dynamic boost|Preventive function monitoring indicates critical operating states before errors occur|High efficiency and long service life, with low power dissipation and low heating|Space savings in the control cabinet, thanks to a narrow, slim-line design|Fast and easy startup, thanks to tool-free Push-in connection technology