Description
Panel feed-through terminal block, connection method: Screw connection with tension sleeve, Screw connection with tension sleeve, number of positions: 1, load current: 57 A, cross section: 0.5 mm2 – 16 mm2, connection direction of the conductor to plug-in direction: 0 °, width: 10.1 mm
Product type | Panel feed-through terminal block |
Number of positions | 1 |
Pitch | 10.1 mm |
Number of connections | 2 |
Number of rows | 1 |
Number of potentials | 1 |
Insulation characteristics | |
Overvoltage category | III |
Degree of pollution | 3 |
Nominal current IN | 57 A |
Nominal voltage UN | 400 V (With metal panels of 1 mm … 2.5 mm) |
Degree of pollution | 3 |
Rated voltage (III/3) | 400 V |
Rated surge voltage (III/3) | 6 kV |
Rated voltage (III/2) | 500 V |
Rated surge voltage (III/2) | 6 kV |
Connection technology | |
Connector system | HDFK 10 |
Nominal cross section | 10 mm² |
Conductor connection exterior | |
Connection method | Screw connection with tension sleeve |
Connection direction of the conductor to plug-in direction | 0 ° |
Conductor cross section solid | 0.5 mm² … 16 mm² |
Conductor cross section flexible | 0.5 mm² … 10 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² … 10 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² … 10 mm² |
2 conductors with same cross section, solid | 0.5 mm² … 4 mm² |
2 conductors with same cross section, flexible | 0.5 mm² … 4 mm² |
2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.5 mm² … 2.5 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² … 6 mm² |
Internal cylindrical gage | B6 |
Stripping length | 10 mm |
Tightening torque | 1.5 Nm … 1.8 Nm |
Conductor connection interior | |
Connection method | Screw connection with tension sleeve |
Connection direction of the conductor to plug-in direction | 0 ° |
Conductor cross section solid | 0.5 mm² … 16 mm² |
Conductor cross section flexible | 0.5 mm² … 10 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² … 10 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² … 10 mm² |
2 conductors with same cross section, solid | 0.5 mm² … 4 mm² |
2 conductors with same cross section, flexible | 0.5 mm² … 4 mm² |
2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.5 mm² … 2.5 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² … 6 mm² |
Internal cylindrical gage | B6 |
Stripping length | 10 mm |
Tightening torque | 1.5 Nm … 1.8 Nm |
Material data – contact | |
Note | WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 |
Contact material | Cu alloy |
Surface characteristics | tin-plated |
Material data – housing | |
Color (Housing) | gray (7042) |
Insulating material | PA |
Insulating material group | I |
CTI according to IEC 60112 | 600 |
Flammability rating according to UL 94 | V0 |
Glow wire flammability index GWFI according to EN 60695-2-12 | 850 |
Glow wire ignition temperature GWIT according to EN 60695-2-13 | 775 |
Temperature for the ball pressure test according to EN 60695-10-2 | 125 °C |
Material data – actuating element | |
Color () | () |
Safety note | |
Safety note | • Only electrically qualified personnel may install and operate the product. To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering. |
• Observe the technical data provided here and refer to the documents listed under “Downloads”. The download area contains important information, such as installation notes, technical drawings, and 3D data. | |
• The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection. | |
There is no electrical contact to the housing. Make sure that protective grounding is provided for green/yellow color variants and articles marked with PE. |
Dimensional drawing | |
Pitch | 10.1 mm |
Width [w] | 10.1 mm |
Height [h] | 31 mm |
External dimensions | |
Width [w] | 10.1 mm |
Height [h1] | 31 mm |
Length [l1] | 24.5 mm |
Internal dimensions | |
Width [w] | 10.1 mm |
Height [h2] | 28.5 mm |
Length [l2] | 18 mm |
Test for conductor damage and slackening | |
Specification | IEC 60947-7-1:2009-04 |
Result | Test passed |
Pull-out test | |
Specification | IEC 60947-7-1:2009-04 |
Conductor cross section/conductor type/tractive force setpoint/actual value | 0.5 mm² / solid / > 20 N |
0.5 mm² / flexible / > 20 N | |
16 mm² / solid / > 100 N | |
10 mm² / flexible / > 90 N |
Temperature-rise test | |
Specification | IEC 60947-7-1:2009-04 |
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Short-time withstand current | |
Specification | IEC 60947-7-1:2009-04 |
Air clearances and creepage distances | 1. Insulation coordination | |
Application | Metal wall 1.0 mm … 2.5 mm |
Specification | IEC 60947-7-1:2009-04 |
Insulating material group | I |
Comparative tracking index (IEC 60112) | CTI 600 |
Rated insulation voltage (III/3) | 400 V |
Rated surge voltage (III/3) | 6 kV |
minimum clearance value – non-homogenous field (III/3) | 5.5 mm |
minimum creepage distance (III/3) | 5.5 mm |
Rated insulation voltage (III/2) | 500 V |
Rated surge voltage (III/2) | 6 kV |
minimum clearance value – non-homogenous field (III/2) | 5.5 mm |
minimum creepage distance (III/2) | 5.5 mm |
Rated insulation voltage (II/2) | 1000 V |
Rated surge voltage (II/2) | 6 kV |
minimum clearance value – non-homogenous field (II/2) | 5.5 mm |
minimum creepage distance (II/2) | 5.5 mm |
Air clearances and creepage distances | 2. Insulation coordination | |
Application | Metal wall > 2.5 mm … 4.0 mm |
Specification | IEC 60947-1:2007-06 + A1:2010-12 |
Insulating material group | I |
Comparative tracking index (IEC 60112) | CTI 600 |
Rated insulation voltage (III/3) | 250 V |
Rated surge voltage (III/3) | 4 kV |
minimum clearance value – non-homogenous field (III/3) | 3 mm |
minimum creepage distance (III/3) | 3.2 mm |
Rated insulation voltage (III/2) | 250 V |
Rated surge voltage (III/2) | 4 kV |
minimum clearance value – non-homogenous field (III/2) | 3 mm |
minimum creepage distance (III/2) | 3 mm |
Rated insulation voltage (II/2) | 500 V |
Rated surge voltage (II/2) | 4 kV |
minimum clearance value – non-homogenous field (II/2) | 3 mm |
minimum creepage distance (II/2) | 3 mm |
Air clearances and creepage distances | 3. Insulation coordination | |
Application | Plastic panel |
Specification | IEC 60947-1:2007-06 + A1:2010-12 |
Insulating material group | I |
Comparative tracking index (IEC 60112) | CTI 600 |
Rated insulation voltage (III/3) | 500 V |
Rated surge voltage (III/3) | 6 kV |
minimum clearance value – non-homogenous field (III/3) | 5.5 mm |
minimum creepage distance (III/3) | 6.3 mm |
Rated insulation voltage (III/2) | 500 V |
Rated surge voltage (III/2) | 6 kV |
minimum clearance value – non-homogenous field (III/2) | 5.5 mm |
minimum creepage distance (III/2) | 5.5 mm |
Rated insulation voltage (II/2) | 1000 V |
Rated surge voltage (II/2) | 6 kV |
minimum clearance value – non-homogenous field (II/2) | 5.5 mm |
minimum creepage distance (II/2) | 5.5 mm |
Air clearances and creepage distances | 4. Insulation coordination | |
Application | Plastic panel with DP-HDFK 10-5,5 |
Specification | IEC 60947-1:2007-06 + A1:2010-12 |
Insulating material group | I |
Comparative tracking index (IEC 60112) | CTI 600 |
Rated insulation voltage (III/3) | 800 V |
Rated surge voltage (III/3) | 8 kV |
minimum clearance value – non-homogenous field (III/3) | 8 mm |
minimum creepage distance (III/3) | 10 mm |
Rated insulation voltage (III/2) | 1000 V |
Rated surge voltage (III/2) | 8 kV |
minimum clearance value – non-homogenous field (III/2) | 8 mm |
minimum creepage distance (III/2) | 8 mm |
Rated insulation voltage (II/2) | 1000 V |
Rated surge voltage (II/2) | 8 kV |
minimum clearance value – non-homogenous field (II/2) | 8 mm |
minimum creepage distance (II/2) | 8 mm |