Description
Output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA … 20 mA signals to a load in the safe area. 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3) in accordance with IEC 61508, Push-in connection.
Product type | Output signal conditioner |
Type | Signal conditioners with SIL functional safety |
Configuration | DIP switches |
Insulation characteristics | |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation | 3-way isolation |
Signal transmission behavior | In = Out |
Step response (10-90%) | < 140 µs (for 4 mA … 20 mA step) |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | ≤ 0.005 %/K |
Maximum transmission error | 0.1 % (of final value) |
Transmission error, typical | ≤ 0.05 % (of final value) |
Electrical isolation Input/output | |
Rated insulation voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Altitude | ≤ 2000 m |
Electrical isolation Input/power supply | |
Rated insulation voltage | 50 Vrms |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation in accordance with IEC/EN 61010-1 |
Altitude | ≤ 2000 m |
Electrical isolation Output/supply | |
Rated insulation voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Altitude | ≤ 2000 m |
Electrical isolation Input 1/input 2, output 1/output 2 | |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Altitude | ≤ 2000 m |
Supply | |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC … 30 V DC (24 V DC, -20 % … +25 %) |
Max. current consumption | < 45 mA (at 24 V DC / 20 mA) |
Power dissipation | < 0.8 W (at 24 V DC / 20 mA) |
Power consumption | ≤ 1.1 W (at 24 V DC / 20 mA) |
Signal: Current | |
Current input signal | 0 mA … 20 mA (Function (short-circuit detection off)) |
0.2 mA … 20 mA (Function (short-circuit detection on)) | |
4 mA … 20 mA (Safety) | |
0 mA … 24 mA (Underload/overload range) | |
Input current | ≤ 30 mA |
Input impedance | > 1 MΩ (If there is a line fault) |
Line fault detection | > 0.2 mA (Response threshold of input current) |
Voltage drop | < 2.4 V (at 20 mA) |
Signal: Current | |
Current output signal | 0 mA … 20 mA (Function (short-circuit detection off)) |
0.2 mA … 20 mA (Function (short-circuit detection on)) | |
4 mA … 20 mA (Safety) | |
0 mA … 24 mA (Underload/overload range) | |
Load | 100 Ω … 700 Ω (20 mA (short-circuit detection on)) |
100 Ω … 650 Ω (20.5 mA (short-circuit detection on)) | |
100 Ω … 500 Ω (24 mA (short-circuit detection on)) | |
0 Ω … 700 Ω (20 mA (short-circuit detection off)) | |
0 Ω … 650 Ω (20.5 mA (short-circuit detection off)) | |
0 Ω … 500 Ω (24 mA (short-circuit detection off)) | |
Output ripple | < 20 mVrms |
Non-load voltage | ≤ 27 V |
Line fault detection | > 10 kΩ (Line break) |
< 50 Ω (Short circuit) |
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section solid | 0.2 mm² … 1.5 mm² |
Conductor cross section flexible | 0.2 mm² … 1.5 mm² |
Conductor cross section AWG | 24 … 16 |
COMBICON connection | |
Max. diameter | 2 mm |
Data communication (bypass) | |
HART function | Yes |
Protocols supported | HART-transparent |
Status display | Green LED (supply voltage) |
Functionality | |
Configuration | DIP switches |
Width | 12.5 mm |
Height | 116 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing material | PA 6.6-FR |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -40 °C … 70 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Permissible humidity (operation) | 5 % … 95 % (non-condensing) |
Altitude range (≤ 2000 m (Ex)) | |
Description | Ex applications |
Altitude | ≤ 2000 m (For use at altitudes ≥2000 m above sea level, see data sheet.) |
Ambient temperature (operation) | -40 °C … 70 °C |
Rated insulation voltage | 320 V (Power supply, input / output) |
Altitude range (≤ 3000 m (Ex)) | |
Description | Ex applications |
Height range | > 2000 m … 3000 m |
Ambient temperature (operation) | -40 °C … 60 °C |
Rated insulation voltage | 190 V (Power supply, input / output) |
Altitude range (≤ 4000 m (Ex)) | |
Description | Ex applications |
Height range | > 3000 m … 4000 m |
Ambient temperature (operation) | -40 °C … 55 °C |
Rated insulation voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 5000 m (Ex)) | |
Description | Ex applications |
Height range | > 4000 m … 5000 m |
Ambient temperature (operation) | -40 °C … 45 °C |
Rated insulation voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 2000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Altitude | ≤ 2000 m (For use at altitudes ≥2000 m above sea level, see data sheet.) |
Ambient temperature (operation) | -40 °C … 70 °C |
Rated insulation voltage | 300 V (Power supply, input / output) |
Altitude range (≤ 3000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Height range | > 2000 m … 3000 m |
Ambient temperature (operation) | -40 °C … 60 °C |
Rated insulation voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 4000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Height range | > 3000 m … 4000 m |
Ambient temperature (operation) | -40 °C … 55 °C |
Rated insulation voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 5000 m) | |
Description | Non-Ex applications (EN 61010-1) |
Height range | > 4000 m … 5000 m |
Ambient temperature (operation) | -40 °C … 45 °C |
Rated insulation voltage | 150 V (Power supply, input / output) |
CE | |
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX | |
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | BVS 20 ATEX E 003 X |
UKCA Ex (UKEX) | |
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | PxCIF21UKEx2908065X |
IECEx | |
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx BVS 20.0003X |
CCC / China-Ex | |
Identification | Ex nA IIC T4 Gc |
INMETRO | |
Identification | Ex ec IIC T4 Gc |
Certificate | DNV 21.0092 X |
UL, USA / Canada | |
Identification | UL 61010 Listed |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC T4 | |
Shipbuilding approval | |
Certificate | DNV GL TAA00000AG |
EAC | |
Identification | 2Ex e IIC T4 Gc X |
Certificate | RU C-DE.HB49.B.00145/21 |
Safety Integrity Level (SIL, IEC 61508) | |
Identification | 2 |
Systematic Capability | |
Identification | 3 |
DNV GL data | |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
ECLASS
ECLASS-9.0 | 27210120 |
ECLASS-10.0.1 | 27210120 |
ECLASS-11.0 | 27210120 |
ETIM
ETIM 8.0 | EC002653 |
UNSPSC
UNSPSC 21.0 | 39121000 |