Description
FO converter with integrated optical diagnostics, alarm contact, for PROFIBUS up to 12 Mbps, T-coupler with two FO interfaces (BFOC), 850 nm, for PCF/fiberglass cable (multimode)
Utilization restriction | |
EMC note | EMC: class A product, see manufacturer’s declaration in the download area |
Utilization restriction | |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Product type | Media converter |
MTTF | 212 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
150 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
86 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) | |
MTBF | 149 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
24 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical isolation | VCC // RS-485 |
Maximum power dissipation for nominal condition | 2.88 W |
Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) |
Supply | |
Supply voltage range | 18 V DC … 30 V DC (via pluggable COMBICON screw terminal block) |
Nominal supply voltage | 24 V DC (in acc. with UL) |
Typical current consumption | 120 mA (24 V DC) |
Max. current consumption | 130 mA |
≤ 2 A (For operation in a joining station, via the DIN rail connector) | |
Connection method | COMBICON plug-in screw terminal block |
Switching | |
Output name | Relay output |
Output description | Alarm output |
Number of outputs | 1 |
Maximum switching voltage | 60 V DC (Resistive Load, General Load) |
30 V AC (Resistive load) | |
42 V AC (peak, resistive load) | |
Limiting continuous current | 0.46 A |
Supply | |
Connection method | COMBICON plug-in screw terminal block |
Stripping length | 7 mm |
Tightening torque | 0.56 Nm … 0.79 Nm |
Bit distortion, input | ± 35 % (permitted) |
Bit distortion, output | < 6.25 % |
Bit delay | < 1 bit (DIP 7 = OFF, standard operation) |
11 bit (DIP 7 = ON, redundancy operation) | |
Signal | PROFIBUS |
Data: optical FO | |
No. of channels | 2 |
Transmit capacity, minimum | -4.2 dBm (200/230 µm) |
-17.8 dBm (50/125 µm) | |
-14.6 dBm (62,5/125 µm) | |
Transmission length incl. 3 dB system reserve | 2600 m (with F-G 50/125 2.5 dB/km) |
3300 m (with F-G 62,5/125 3.0 dB/km) | |
800 m (With F-K 200/230 10 dB/km with quick mounting connector) | |
Transmission protocol | Protocol-transparent to the RS-485 interface |
Connection method | B-FOC (ST®) |
Wavelength | 850 nm |
Minimum receiver sensitivity | -30 dBm (50/125 µm) |
Maximum receiver sensitivity | -3 dBm (200/230 µm) |
Transmission medium | PCF fiber |
Multi-mode fiberglass | |
Data: PROFIBUS acc. to IEC 61158, RS-485 2-wire, half duplex, automatic control | |
Serial transmission speed | ≤ 12 Mbps |
Connection method | D-SUB-9 female connector |
Transmission length | ≤ 1200 m (depending on the data rate, with shielded, twisted pair data cable) |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section solid min. | 0.2 mm² |
Max. AWG conductor cross section, flexible | 14 |
Min. AWG conductor cross section, flexible | 24 |
Single-wire/terminal point, solid AWG max. | 14 |
Single-wire/terminal point, solid AWG min. | 24 |
Transmission medium | Copper |
File format/coding | UART (11 Bit, NRZ) |
Data direction switching | Automatic control |
Output nominal voltage | 5 V ±0.25 (50 mA) |
Width | 35 mm |
Height | 99 mm |
Depth | 106 mm |
Material | PA 6.6-FR (Housing) |
FO cable | |
Fiber types | 50/125 µm |
62.5/125 µm | |
Fiberglass |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -20 °C … 60 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Altitude | ≤ 5000 m (For restrictions, see the manufacturer’s declaration for altitude operation) |
≤ 2000 m (Hazardous locations) | |
Permissible humidity (operation) | 30 % … 95 % (non-condensing) |
CE | |
Certificate | CE-compliant |
EAC | |
Identification | EAC |
ATEX | |
Identification | II 3 G Ex nA nC IIC T4 Gc X |
Note | Please follow the special installation instructions in the documentation! |
ATEX, FO interface | |
Identification | II (2) G [Ex op is Gb] IIC |
II (2) D [Ex op is Db] IIIC | |
Certificate | PTB 06 ATEX 2042 U |
Note | Please follow the special installation instructions in the documentation! |
UL, USA / Canada | |
Identification | Class I, Zone 2, AEx nc IIC T5 |
Class I, Zone 2, Ex nC nL IIC T5 X | |
Class I, Div. 2, Groups A, B, C, D | |
PROFIBUS interoperability | |
Note | Tested by independent PNO test laboratory (PN059-485-01) |
ABB certification | |
Identification | IndustrialIT enabled |
Note | This certification is a trademark of ABB. |
Corrosive gas test | |
Identification | ISA-S71.04-1985 G3 Harsh Group A |
Shipbuilding | |
Identification | DNV GL |
DNV GL data | |
Temperature | B |
Humidity | A |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 |
Noise immunity | EN 61000-6-2:2005 |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | ± 6 kV |
Discharge in air | ± 8 kV |
Comments | Criterion B |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Field intensity | 10 V/m |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | ± 2 kV |
Signal | ± 2 kV |
Comments | Criterion B |
Surge current load (surge) | |
Standards/regulations | EN 61000-4-5 |
Surge current load (surge) | |
Input | ± 0.5 kV |
Signal | ± 1 kV |
Comments | Criterion B |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Comments | Criterion A |
Voltage | 10 V |
Emitted interference | |
Standards/regulations | EN 55011 |
Comments | Class A, industrial applications |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Air clearances and creepage distances | |
Standards/regulations | DIN EN 60664-1 |
VDE 0110-1 | |
DIN EN 50178 | |
EN 60950 |
Mounting type | DIN rail mounting |
Item number | 2708261 |
Packing unit | 1 pc |
Minimum order quantity | 1 pc |
Sales Key | DNC |
Product Key | DNC211 |
Catalog Page | Page 431 (C-6-2019) |
GTIN | 4017918973964 |
Weight per Piece (including packing) | 265.2 g |
Weight per Piece (excluding packing) | 265.2 g |
Customs tariff number | 85176200 |
Country of origin | DE |
ECLASS
ECLASS-9.0 | 19170114 |
ECLASS-10.0.1 | 19170132 |
ECLASS-11.0 | 19170411 |
ETIM
ETIM 8.0 | EC001467 |
UNSPSC
UNSPSC 21.0 | 43201500 |
Can be combined with the PSI copper repeater in a modular way using DIN rail connectors|Supply voltage and data signals routed through the DIN rail connectors|Connections can be plugged in via a COMBICON screw terminal block|Automatic data rate detection or fixed data rate setting via DIP switches|Redundant power supply|High-quality electrical isolation between all interfaces (PROFIBUS // fiber optic ports // power supply // DIN rail connector)|Approved for use in zone 2|Integrated optical diagnostics for continuous monitoring of FO paths|Intrinsically safe fiber optic interface (Ex op is) for direct connection to devices in zone 1|Floating switch contact for advance warning of critical FO paths|Suitable for all data rates up to 12 Mbps|Bit retiming for any cascading depth|Shipbuilding approval in accordance with DNV GL