Description
LI0737–K-00KQPKG/US
Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 2 |
Factory setting |
hydrous media |
Probe length L [mm] |
737 |
Application |
Special feature |
Gold-plated contacts |
Media |
Liquids |
Dielectric constant of the medium |
> 1,8 |
Recommended media |
water; hydrous media; oils; oil-based media |
Cannot be used for |
See operating instructions, chapter “Intended use”. |
Medium temperature [°C] |
-25…85 |
Pressure rating [bar] |
0.5 |
Vacuum resistance [mbar] |
-500 |
Electrical data |
Operating voltage [V] |
9.6…35 DC; (IO-Link: 18…30 DC) |
Current consumption [mA] |
< 15 |
Protection class |
III |
Reverse polarity protection |
yes |
Power-on delay time [s] |
< 1 |
Measuring principle |
capacitive |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2 |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal; IO-Link |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] |
2.5 |
Permanent current rating of switching output DC [mA] |
100 |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
Measuring/setting range |
Factory setting |
hydrous media |
Probe length L [mm] |
737 |
Active range A [mm] |
28 |
Temperature measurement |
Measuring range [°C] |
-25…85 |
Accuracy / deviations |
Temperature measurement |
Accuracy [K] |
1,5 |
Resolution [K] |
0.1 |
Dynamic response T09 [s] |
240 |
Response times |
Response time [s] |
< 0.3 |
Interfaces |
Communication interface |
IO-Link |
Unterstützte Masterportklasse |
A |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.1 |
SDCI standard |
IEC 61131-9 |
Profiles |
Smart Sensor ED2: Identification and Diagnosis (0x4000), Measurement Data Channel (0x800A) |
SIO mode |
yes |
Process data analogue |
5 |
Process data binary |
2 |
Min. process cycle time [ms] |
4.5 |
Supported DeviceIDs |
Type of operation |
DeviceID |
Default |
1053 |
|
Operating conditions |
Ambient temperature [°C] |
-25…85 |
Storage temperature [°C] |
-25…85 |
Protection |
IP 68; IP 69K; (7 days / 3 m water depth / 0.3 bar: IP 68) |
Tests / approvals |
EMC |
DIN EN 61000-6-2 |
|
DIN EN 61000-6-3 |
in a closed metal tank |
DIN EN 61000-6-4 |
in plastic or open metal tanks |
|
Shock resistance |
DIN EN 60068-2-27 |
12 g (11 ms) |
|
Vibration resistance |
DIN EN 60068-2-6 |
5 g (10…2000 Hz) |
|
MTTF [years] |
433 |
UL approval |
UL Approval no. |
H013 |
File number UL |
E174191 |
|
Mechanical data |
Weight [g] |
510.4 |
Materials |
PP reinforced fibre |
Materials (wetted parts) |
PP |
Probe diameter [mm] |
16 |
Displays / operating elements |
Display |
operation |
LED, green |
switching status |
LED, yellow |
|
Operating elements |
inductive programming button |
|
|
Remarks |
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |