Description
PI-1-1BREA01-MFRKG/US/ /P
Product characteristics |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Measuring range |
-1…1 bar |
-1000…1000 mbar |
-14.5…14.5 psi |
-100…100 kPa |
|
Process connection |
threaded connection G 1 external thread sealing cone Attention: The unit must only be installed in a process connection for G1 sealing cone.; The G1A sealing cone of the unit is only suited for adapters with metal end stop. |
Application |
Special feature |
Gold-plated contacts |
Application |
flush mountable for the food and beverage industry |
Media |
viscous media and liquids with suspended particles; liquids and gases |
Medium temperature [°C] |
-25…125; (145 max. 1h) |
Min. bursting pressure |
30000 mbar |
435 psi |
3000 kPa |
|
Pressure rating |
10000 mbar |
145 psi |
1000 kPa |
|
Vacuum resistance [mbar] |
-1000 |
Type of pressure |
relative pressure; vacuum |
MAWP (for applications according to CRN) [bar] |
10 |
Electrical data |
Min. insulation resistance [MΩ] |
100; (500 V DC) |
Protection class |
III |
Reverse polarity protection |
yes |
Measuring principle |
hydrostatic |
Integrated watchdog |
yes |
2-wire |
Operating voltage [V] |
20…32 DC |
Current consumption [mA] |
3.6…21 |
Power-on delay time [s] |
1 |
3-wire |
Operating voltage [V] |
18…32 DC |
Current consumption [mA] |
< 45 |
Power-on delay time [s] |
0.5 |
Inputs / outputs |
Number of inputs and outputs |
Number of digital outputs: 2; Number of analogue outputs: 1 |
Outputs |
Total number of outputs |
2 |
Output signal |
switching signal; analogue signal; IO-Link; (configurable) |
Electrical design |
PNP/NPN |
Number of digital outputs |
2 |
Output function |
normally open / normally closed; (parameterisable) |
Number of analogue outputs |
1 |
Analogue current output [mA] |
4…20, invertible; (scalable) |
Short-circuit protection |
yes |
Type of short-circuit protection |
pulsed |
Overload protection |
yes |
2-wire |
Max. load [Ω] |
300 |
3-wire |
Max. voltage drop switching output DC [V] |
2 |
Permanent current rating of switching output DC [mA] |
250 |
Switching frequency DC [Hz] |
125 |
Max. load [Ω] |
(Ub – 10 V) / 20 mA |
Measuring/setting range |
Measuring range |
-1…1 bar |
-1000…1000 mbar |
-14.5…14.5 psi |
-100…100 kPa |
|
Set point SP |
-998…1000 mbar |
-14.45…14.5 psi |
-99.8…100 kPa |
|
Reset point rP |
-1000…998 mbar |
-14.5…14.45 psi |
-100…99.8 kPa |
|
Analogue start point |
-1000…500 mbar |
-14.5…7.25 psi |
-100…50 kPa |
|
Analogue end point |
-500…1000 mbar |
-7.25…14.5 psi |
-50…100 kPa |
|
In steps of |
|
Factory setting |
|
SP1 = -500 mbar |
rP1 = -540 mbar |
|
SP2 = 500 mbar |
rP2 = 460 mbar |
|
ASP = -1000 mbar |
AEP = 1000 mbar |
|
Accuracy / deviations |
Switch point accuracy [% of the span] |
< ± 0,2; (Turn down 1:1) |
Repeatability [% of the span] |
< ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span] |
< ± 0,2; (Turn down 1:1 , linearity, incl. hysteresis and repeatability , limit value setting to DIN EN IEC 62828-1) |
Linearity deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
Hysteresis deviation [% of the span] |
< ± 0,15; (Turn down 1:1) |
Long-term stability [% of the span] |
< ± 0,1; (Turn down 1:1; per year) |
Temperature coefficient zero point [% of the span / 10 K] |
< ± 0,05; (0…70 °C) |
Temperature coefficient span [% of the span / 10 K] |
< ± 0,15; (0…70 °C) |
Response times |
Damping process value dAP [s] |
0…30 |
Damping for the analogue output dAA [s] |
0.01…99.99 |
2-wire |
Step response time analogue output [ms] |
45 |
3-wire |
Min. response time of switching output (dAP) [ms] |
3 |
Step response time analogue output [ms] |
7 |
Interfaces |
Communication interface |
IO-Link |
Transmission type |
COM2 (38,4 kBaud) |
IO-Link revision |
1.0 |
Profiles |
no profile |
SIO mode |
yes |
Required master port type |
A |
Process data analogue |
1 |
Process data binary |
2 |
Min. process cycle time [ms] |
2.3 |
Supported DeviceIDs |
Type of operation |
DeviceID |
Default |
258 |
|
Operating conditions |
Ambient temperature [°C] |
-25…80 |
Storage temperature [°C] |
-40…100 |
Protection |
IP 67; IP 68; IP 69K |
Tests / approvals |
EMC |
EN 61000-4-2 ESD |
4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated |
10 V/m |
EN 61000-4-4 Burst |
2 kV |
EN 61000-4-5 Surge |
0,5/1 kV |
EN 61000-4-6 HF conducted |
10 V |
|
Shock resistance |
DIN IEC 68-2-27 |
50 g (11 ms) |
|
Vibration resistance |
DIN IEC 68-2-6 |
20 g (10…2000 Hz) |
|
MTTF [years] |
148.66 |
Note on approval |
factory certificate available as download at www.factory-certificate.ifm |
|
Mechanical data |
Weight [g] |
379 |
Materials |
stainless steel (1.4404 / 316L); FKM; PTFE; PBT; PEI; PFA |
Materials (wetted parts) |
ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE |
Min. pressure cycles |
100 million |
Process connection |
threaded connection G 1 external thread sealing cone Attention: The unit must only be installed in a process connection for G1 sealing cone.; The G1A sealing cone of the unit is only suited for adapters with metal end stop. |
Displays / operating elements |
Display |
Display unit |
LED, green |
switching status |
LED, yellow |
function display |
alphanumeric display, 4-digit |
measured values |
alphanumeric display, 4-digit |
|
Display unit |
mbar; kPa; psi; inH2O; mWS; % of the span |
Remarks |
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |